Open the Well Pressure Tank Sizer →Read the well water guide
Free, no sign-up, runs in your browser at well-pressure-tank-sizer.pages.dev.
It answers
“What size pressure tank do I need for my pump and switch setting?” and “Is my current tank too small?”
You get
- Required drawdown in gallons
- The smallest tank on the Amtrol Well-X-Trol reference table that meets it, with model
- Precharge setting (cut-in − 2 psi)
- A warning if your current tank looks undersized
- The full drawdown reference table with your pick highlighted
What to have ready (and where to find it)
| Input | Where to find it |
|---|---|
| Pump flow (GPM) | Well driller’s log, installer invoice, or the pump model’s spec sheet. Nameplate GPM wins over guesses. |
| Minimum run time | 1 minute is the common target; 2 minutes is safer on larger pumps. Use the pump maker’s figure if given. |
| Pressure switch setting | Watch the gauge through one cycle: low point is cut-in, high point is cut-out (e.g. 30/50, 40/60). |
| Current tank size (optional) | Label on the tank. |
How the math works
drawdown needed = GPM × minimum run minutes
pick = smallest tank whose published drawdown at your
switch setting ≥ drawdown needed
precharge = cut-in − 2 psi (tank empty)
20/40 settings = estimated (~15% above 30/50; not on the card)
Worked example
10 GPM × 1 min = 10 gal needed at 30/50
WX-203 (32 gal) ≈ 9.9 gal → short
WX-205 (34 gal) ≈ 10.5 gal → pick · precharge 28 psi
Drawdowns from Amtrol Well-X-Trol specifications card MC7025 as published in the sizer.
Limits to know
- Drawdowns come from one brand’s published card. Other brands differ; check the chart for the tank you buy.
- A waterlogged tank acts small whatever its label. Check precharge before replacing.
- Constant-pressure (variable-speed) systems follow their own tank and precharge rules.
Run your own numbers
The full tool handles your exact loads and settings, with explanations next to every result.